CR8000
Micro-module products
Back to Micro-Modules
CR8000
Micro-module products
CR8000
The CR8000 micro-modular data center is a new generation of high-efficiency, energy-saving data center, adopting an All-In-One design concept, integrated design approach, and extremely simplified deployment mode. It integrates the cabinet system, power supply and distribution system, cooling system, monitoring system, etc., meeting the deployment needs of various medium and large integrated delivery computer rooms. The micro-modular data center features standardized design, standardized components, prefabrication in factories, and modular deployment, effectively reducing customer communication costs, saving delivery time, and providing customers with time, effort, and peace of mind.
Technical specifications
Name Specification
Overall Characteristics Aisle Specifications:
Single row: L×2200-2400×2000-2200, L≤15m;
Double row: L×3200-3600×2000-2200, L≤15m;
Cabinet depth supports 1100mm, 1200mm;
Cabinet height supports 2000mm, 2200mm;
Enclosed aisle width supports 1200mm and 1800mm
Overall Characteristics Total cabinet positions:
Single row: 25 positions; Double row: 50 positions
Overall Characteristics Installation method: Raised floor installation, or direct installation on cement floor.
Overall Characteristics Power Supply System: 380/400/415V AC, 50/60Hz, 3Ph+N+PE
Power Supply and Distribution System UPS Input Voltage: 380/400/415Vac, 50/60Hz, 3Ph+N+PE
Power Supply and Distribution System UPS rated capacity: 20-600 kVA
Power Supply and Distribution System UPS configuration modes: N, N+1, 2N
Power Supply and Distribution System UPS input power factor: ≥0.99
Power Supply and Distribution System UPS output power factor: 1
Power Supply and Distribution System Maintenance method: Online hot-swap maintenance
Power Supply and Distribution System IT cabinet power supply mode: utility/diesel generator + utility/diesel generator; UPS + UPS; UPS + utility/diesel generator
refrigeration system Air Conditioner Selection: In-row air-cooled / chilled water, room-level air-cooled / chilled water
refrigeration system Cooling method: air cooling, chilled water
refrigeration system Air conditioner installation method: indoor unit installed on a raised floor, outdoor unit installed on a level concrete surface.
refrigeration system Fan type: EC fan
refrigeration system Air supply mode: Row-level: horizontal air supply; Room-level: up/down air supply
refrigeration system Air conditioner indoor unit dimensions: Refer to the selection table for details.
Monitoring Management System Functional modules: Environmental monitoring module, Power monitoring module, Management monitoring module (optional)
Monitoring Management System Access methods:
Remote web access, local touch screen (external: 43-inch large screen;
embedded: other sizes), mobile app (optional)
Monitoring Management System Alarm modes: local audible and visual alarm, SMS alarm, email alarm, phone alarm, WeChat alarm
Rack System Dimensions: Width * Depth * Height (mm): 600/800 × 1100/1200 × 2000/2200
Rack System Available space: 42U/47U
Rack System Certification status: static load-bearing, dynamic load-bearing, seismic resistance