| Name | Specification |
|---|---|
| Overall Characteristics | Aisle Specifications: Single row: L×2200-2400×2000-2200, L≤15m; Double row: L×3200-3600×2000-2200, L≤15m; Cabinet depth supports 1100mm, 1200mm; Cabinet height supports 2000mm, 2200mm; Enclosed aisle width supports 1200mm and 1800mm |
| Overall Characteristics | Total cabinet positions: Single row: 25 positions; Double row: 50 positions |
| Overall Characteristics | Installation method: Raised floor installation, or direct installation on cement floor. |
| Overall Characteristics | Power Supply System: 380/400/415V AC, 50/60Hz, 3Ph+N+PE |
| Power Supply and Distribution System | UPS Input Voltage: 380/400/415Vac, 50/60Hz, 3Ph+N+PE |
| Power Supply and Distribution System | UPS rated capacity: 20-600 kVA |
| Power Supply and Distribution System | UPS configuration modes: N, N+1, 2N |
| Power Supply and Distribution System | UPS input power factor: ≥0.99 |
| Power Supply and Distribution System | UPS output power factor: 1 |
| Power Supply and Distribution System | Maintenance method: Online hot-swap maintenance |
| Power Supply and Distribution System | IT cabinet power supply mode: utility/diesel generator + utility/diesel generator; UPS + UPS; UPS + utility/diesel generator |
| refrigeration system | Air Conditioner Selection: In-row air-cooled / chilled water, room-level air-cooled / chilled water |
| refrigeration system | Cooling method: air cooling, chilled water |
| refrigeration system | Air conditioner installation method: indoor unit installed on a raised floor, outdoor unit installed on a level concrete surface. |
| refrigeration system | Fan type: EC fan |
| refrigeration system | Air supply mode: Row-level: horizontal air supply; Room-level: up/down air supply |
| refrigeration system | Air conditioner indoor unit dimensions: Refer to the selection table for details. |
| Monitoring Management System | Functional modules: Environmental monitoring module, Power monitoring module, Management monitoring module (optional) |
| Monitoring Management System | Access methods: Remote web access, local touch screen (external: 43-inch large screen; embedded: other sizes), mobile app (optional) |
| Monitoring Management System | Alarm modes: local audible and visual alarm, SMS alarm, email alarm, phone alarm, WeChat alarm |
| Rack System | Dimensions: Width * Depth * Height (mm): 600/800 × 1100/1200 × 2000/2200 |
| Rack System | Available space: 42U/47U |
| Rack System | Certification status: static load-bearing, dynamic load-bearing, seismic resistance |